Fault mode relay
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
FAULT
Fault relays de-energize when a particular fault condition exists. Parameter D831 shows a
list of active faults.
Table 4-14: Fault Mode Relay Parameters
Parameter
Description
Factory default
P560
System Fault
Fault relay de-energizes while there is a control unit
fault and the option is Both or Relay.
Both
P561
CU Temp Fault
Fault relay de-energizes while the CPU temperature
rises above 65 °C and the option is Both or Relay.
Read-only parameter D844 shows the live
temperature reading.
None
P562
Xmtr Fault
Fault relay de-energizes while a HART transmitter
signals a fault and the option is Both or Relay.
None
P563
Digital Input
Fault relay de-energizes while digital input IN1 or IN2
is triggered and the option is Both or Relay.
See
Fault action required for this feature.
None
Note
Faults can be indicated using the output current if the Current or Both options are
selected.
Related information
Control unit reporting of alarms and faults
Set-up the current output
PV limits mode relay
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
RELAY
→
RELAY 1, RELAY 2, etc.
This relay mode uses the relay On Point and Off Points (e.g. P411 and P412) as high and
low limit alarms for the control unit PV value (D800). The points can be in any order of
value.
The relay is energized while the PV value exceeds the higher limit point value or while it is
below the lower limit point value.
Rate of change mode relay
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
RELAY
→
RELAY 1, RELAY 2, etc.
and
MONITOR
→
[CONTROLLER]
→
READINGS
→
Rate of Change
A rate of change value for the control unit PV value (D800) is calculated every 5 seconds in
units of PV per minute:
Getting started
Reference Manual
January 2021
00809-0100-4841
110
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...