Table 4-17: Auto-sequence Options
Option
Rotation basis
Standby Starts
For Standby mode relays only - rotation is based on how many times the
'leading' relay has been energized compared to parameter P271.
Stdby On Time
For Standby mode relays only - rotation is based on the hours that the 'leading'
relay has been energized compared to parameter P271.
For two Standby mode relays only - rotation is based on the ratio of ON time
for two relays compared to P271.
Stdby Ratio S
For two Standby mode relays only - rotation based on the ratio of starts (times
energized) compared to P271.
Assist Starts
Rotation of 'leading' Assist mode relay is based on how many times it has been
energized compared to P271.
Assist On Time
Rotation of 'leading' Assist mode relay is based on the hours that it has been
energized compared to P271.
Assist Ratio T
For two Assist mode relays only - rotation based on the ratio of ON time for the
two relays compared to P271.
For two Assist mode relays only - rotation based on the ratio of starts (times
energized) compared to P271.
Off
No rotation required.
(1)
Ratio is based on the first two lowest-numbered relays with the same mode.
Related information
Auxiliary functions for relay modes
Energy saving
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
RELAY
→
OVERRIDES
Table 4-18: Energy Saving Parameters
Parameter
Description
Factory default
P275
Engy Save Strt
Set the time of day at which selected relays (P276)
will energize until each relay Off Point is reached. The
energy saving start time is valid for one minute; if
missed by the control unit being in Program mode,
no action is taken when subsequently put into Run
App mode.
0:00 h:m
P276
Engy Save RL
Select relays for the operation associated with
parameter P275.
Each digit represents a relay. Relay RL1 is selected by
editing the first digit to be a “1”. Similarly, relay RL5
is selected with the fifth digit. To de-select a relay,
change the appropriate digit back to a “0”.
00000
Related information
Auxiliary functions for relay modes
Getting started
Reference Manual
January 2021
00809-0100-4841
112
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...