2. Do not mount the control unit on a structure that is subject to vibration, or in a
position where damage may be caused by impact, thermal stress or liquid ingress.
3. The fuse must only be replaced with the type specified.
4. If the equipment is likely to come into contact with aggressive substances, it is the
responsibility of the user to take suitable precautions that prevent it from being
adversely affected, thus ensuring that the type of protection is not compromised.
Aggressive Substances - e.g. acidic liquids or gases that may attack metals or
solvents that may affect polymeric materials.
Suitable Precautions - e.g. regular checks as part of routine inspections or
establishing from the material's data sheet that it is resistant to specific chemicals.
5. The user should not repair this equipment.
6. Terminal 30 (intrinsically safe earth/ground) of the panel mount control unit must
be connected to a high integrity earth/ground point.
For a wall mount control unit, it is recommended that Terminal 30 is connected to a
high integrity earth/ground point.
7. A mains-powered control unit must not be connected to a supply exceeding 250 V
r.m.s. or dc, or to apparatus containing a source of voltage exceeding 250 V r.m.s.
or dc.
8. A direct current (dc) powered control unit must not be connected to a supply
exceeding 30 Vdc or apparatus containing a source of voltage exceeding 30 Vdc.
9. The intrinsically safe outputs of the control unit may be connected to certified
equipment used in a hazardous area.
10. Cable between the control unit and transmitter should be shielded, twisted-pair
with the shield connected to terminal 3 (marked with earth symbol) on the control
unit. The shield should be left unconnected at the transmitter unless there is a
terminal specifically provided for this purpose.
11. Cable runs should be separate from any high voltage or mains cables to avoid
crosstalk or interference.
Related information
Product certifications
Specifications and reference data
Installation
Reference Manual
January 2021
00809-0100-4841
18
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...