![Emerson Rosemount 3490 Series Reference Manual Download Page 100](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788100.webp)
Figure 4-22: Pump 1 and Pump 2 are Off (Level Okay)
A
B
C
D
E
F
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
When the level rises above 5 m (On point, P411), the relay RL1 is energized to start Pump 1
(
).
Figure 4-23: Pump 1 is On (Rising Level Above 5 m)
A
E
F
B
C
D
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
If the level continues to rise and is above 8 m (On point, P421), relay RL2 is energized to
start Pump 2 and assist Pump 1. Relay RL1 stays energized to keep Pump 1 pumping
(
).
Getting started
Reference Manual
January 2021
00809-0100-4841
100
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...