Figure 4-30: Pump 1 and Pump 2 are Off (Level Okay)
A
B
C
D
E
F
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
When the level rises above 5 m (On point, P411), the relay RL1 is energized to start Pump 1
(
).
Figure 4-31: Pump 1 is On (Rising Level Above 5 m)
A
B
C
D
E
F
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
If the level continues to rise and is above 8 m (On point, P421), the relay RL2 is energized
to start Pump 2. Relay RL1 is de-energized to switch off Pump 1 (
).