Digital control voltage-free contact inputs
Allocate an action to IN1 or IN2
Procedure
1. Navigate to
SETUP
→
[CONTROLLER]
→
DIGITAL INPUT
→
DIGITAL INPUT 1 or
DIGITAL INPUT 2
.
2. Use the action selection parameter P340 (for IN1) or P345 (for IN2) to select a
trigger action from the option list.
lists all the options and explains their purpose.
Table 4-4: Digital Input Actions
Action
Action that occurs while digital input is triggered
Free
Digital Input has no allocated action. This is the factory default
setting.
Forces an alarm condition, which is indicated if specified in the
OUTPUT
→
ALARM
menu.
Fault
Forces an fault condition, which is indicated if specified in the
OUTPUT
→
FAULT
menu.
Program mode
Changes the control unit operating mode to Program (open
padlock).
Hold totalizer
Freezes the internal totalizer.
Hold MCU PV
Prevents the control unit PV value (D800) from being updated.
Suppress Alarm
If the digital input is active when an alarm condition is present, a
message is displayed indicating the alarm is being overridden.
Alarm relay is held on.
Displays a user-defined message (P241).
When the next data logging interval elapses, flag the data logged as
a 'bad sample' if the digital input has been active.
Invoke a pump-down operation.
Lock Params
Prevent 'P' prefixed parameters from being edited.
Protect totalizer 1
Prevent totalizer 1 from being reset.
Reset totalizer 2
Reset totalizer 2.
(1)
for information about alarms and features they affect.
(2)
for how to indicate fault conditions using a relay output
(3)
SETUP
→
[CONTROLLER]
→
APPLICATION
→
Message
.
(4)
Data logging is available on the Rosemount 3493.
(5)
The pump-down feature is available on the Rosemount 3491 and Rosemount 3492. See
Pump-down (Rosemount 3491 and 3492 only)
for further information.
(6)
Totalizer 2 is available on the Rosemount 3492 and Rosemount 3493.
3. Use the delay parameter P341 (for IN1) or P346 (for IN2) if a delay is needed before
an action is performed. The setting format is m:s (minutes and seconds).
Getting started
Reference Manual
January 2021
00809-0100-4841
84
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...