4.4.16
Reset the totalizer
Prerequisites
The totalizer may have password (PIN) protection to prevent unauthorized persons from
re-setting the total.
Procedure
1. Navigate to
MONITOR
→
[CONTROLLER]
→
READINGS
→
TOTALIZER
.
2. To re-set a totalizer to zero, display the Totalizer Count parameter D828 and then
select the button corresponding to
Reset
command on display line 4.
Related information
4.4.17
Display configuration options
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
DISPLAY
The factory default configuration of the full display can be changed to show different
graphic and text information.
Table 4-37: Display Configuration Parameters
Parameter
Description
Factory default
P570
Display Upper
Select from the multiple-choice list of parameters
(see
). For example, a totalizer count can
be displayed when D828-Totalizer is selected. If it
will fit, the clock time will also be displayed alongside
the selected parameter.
P731-Time
P571
Display Middle
Select from the multiple-choice list of parameters
(see
). For example, the control unit
Secondary Value (SV) value can be displayed when
D801-SV is selected.
D800-PV
P572
Display Lower
Select from the multiple-choice list of parameters
(see
). For example, you can display a user-
defined message (P241) when the 'P241' option is
selected.
Bar graph
P573
Decimal places
Use this to adjust the number of decimal places.
Range 0 to 5. Alternatively, select “Disabled” (Auto)
for the control unit to automatically choose the
number of decimal places for a displayed parameter
value.
3
P574
Display size
Use this to adjust whether the display shows the
Large PV
display after a period of keypad inactivity, or
remains showing the
Full PV
display.
Large
P575
Back light
Select from
On
(always on),
Off
(always off) or
Auto
(goes on when using keypad; goes off after five
minutes of inactivity).
On
Getting started
Reference Manual
January 2021
00809-0100-4841
130
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...