Screen 26
This screen is used to set the thresholds and hysteresis values for the battery’s
Very High Battery Temperature, High Battery Temperature and Low Battery
Temperature alarms.
Additionally, a Very High Battery Temperature Voltage Output level is set in
the Very High Battery Temperature box. Should the programmed temperature
Alarm Level be reached, the system then automatically reduces the output
voltage of the rectifiers to the programmed voltage level in order to prevent
the batteries from sustaining high temperature and high voltage conditions
simultaneously.