Functional description
45
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 4.1 – List of Controller CIP alarms and their default severity
Alarm name
Alarm severity
Alarm LED
Status LED
No Alarm
None
Green
Green
Supervision Unit Internal
Major
Red
Red
CAN Communication
Minor
Yellow
Green
Prio Distribution Fuse
Major
Red
Green
Non Prio Distribution Fuse
Major
Red
Green
Battery Fuse
Major
Red
Green
LVD1 Contactor
Minor
Yellow
Green
LVD2 Contactor
Minor
Yellow
Green
LVD1 Load Disconnect
Major
Red
Green
LVD2 Load Disconnect
Major
Red
Green
Battery Temp. Sensor
Minor
Yellow
Green
Low Battery Temperature
Minor
Yellow
Green
High Battery Temperature
Major
Red
Green
Very High Battery Temp.
Major
Red
Green
Rectifier Power Limit
None
Green
Green
Battery On Discharge BOD
Major
Red
Green
Low Voltage (LV)
Major
Red
Green
High Voltage (HV)
Major
Red
Green
Rectifier Fail
Minor
Yellow
Green
Multiple Rectifier Fail
Major
Red
Green
Rectifier Mains Fault
Major/ Observ.
Red
Green
Mains Fault
Major/ Observ.
Red
Green
Rectifier Fan Fail
Minor
Yellow
Green
Rectifier High Temperature
Minor
Yellow
Green
Rectifier AC Fail
Major/Observ.
Red
Green
System Configuration Fail
Major
Red
Green
4.1.3. System
Manager
CIP
The System Manager CIP is the advanced controller available with the Lorain
CIP and Lorain CIP Access power systems. The operational features of the
System Manager CIP are as follows:
•
graphical LCD screen,
•
local alarm display by means of LED indicators,
•
8 programmable alarm outputs (dry-C contacts), Minor, Major and
Observation being the factory default for outputs 1, 2 and 3,
•
8 programmable alarm inputs,
•
several processed alarms,
•
alarms and events history files,
•
alarm management,
•
built-in web server,