Configuring and operating the system
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
screens; in each of the four screens, press CHNG, use the
and
buttons to
set the parameter (5 to 1200 minutes in increments of 1, 44.0 to 50.0 V cells
in increments of 0.1, 30 to 50% in increments of 1, and 1 to 10000 A in
increments of 1), then save each setting by pressing the APPL button.
5.5.7.13. Load disconnect
This submenu is used to activate or deactivate up to three load disconnect
contactors and to set their operating parameters. To do so, proceed as follows:
•
In the SETTINGS/LOAD DIS screen, press CHNG. In the LOAD DIS/
DISC MODE screen, use the
and
buttons to select the disconnect
mode, “LVD1 Time, LVD2 Time”, “LVD1 Volt, LVD2 Volt”, “LVD1
Time, LVD2 Volt” or “LVD1, LVD2, LVD3 Cap”, then save the
setting by pressing the APPL button.
•
Use the
and
buttons to go successively to the LVD1 DISC US,
LVD1 DISC VOLT, LVD1 DISC DELAY and LVD1 CAPACITY,
screens; in each of the four screens, press CHNG, use the
and
buttons to activate or deactivate the LVD1 contactor and to set its
operating parameter (40.0 to 50.0 V in increments of 0.1, 1 to 100
hours in increments of 1, and 10 to 90% in increments of 1), then save
each setting by pressing the APPL button.
•
Repeat the previous step for the LVD2 contactor, if applicable.
•
For the LVD3 contactor, use the
and
buttons to go successively
to the LVD3 DISC VOLT, LVD3 CAPACITY, and LVD3 RELAY
screens; in each of the three screens, press CHNG, use the
and
buttons to set its operating parameter (40.0 to 50.0 V in increments
of 0.1, 10 to 90% in increments of 1, and the number of the selected
output relay to operate the contactor in increments of 1), then save each
setting by pressing the APPL button.
Note 1:
The LVD1 and LVD2 contactors are connected to the J7 and J8
connectors respectively on the controller interface card as illustrated in
Note 2:
If a 3
rd
LVD contactor is used, it must be connected to an output
relay. The LVD3 can be enabled only if “LVD1, LVD2, LVD3 CAP” is
selected in the DISC MODE screen.
•
Use the
and
buttons to go to the NOM BATT CAP screen; press
CHNG, use the
and
buttons to set the nominal battery capacity
parameter (1 to 10000 A in increments of 1).
5.5.8. Maintenance
menu
This menu is used to inhibit outgoing alarms, clear logs and active alarms,
start a manual voltage boost, start a manual battery test, and start a LED test.