Configuring and operating the system
107
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Screen 32
This screen is used to enter the alarm information for the selected digital
input. To do so, proceed as follows:
•
enter the alarm name in the first field,
•
select the applicable severity (MAJOR, MINOR, OBSERVATION or
None) for this alarm in the Alarm Severity drop-list menu,
•
select the associated LED color (Red, Yellow or None) for this alarm in
the Alarm LED drop-list menu,
•
select the alarm activation level (0 V or –48 V) for this specific alarm,
and
•
click on the
button to confirm the new parameters.
To deactivate an activated digital input, enter the above screen and erase the
alarm name, select “None” in the alarm severity and 0 V in the Alarm
Activation field, then Alarm LED fields, and click on the
button.
5.6.5.16. Output relays
The System Manager CIP provides eight user-programmable output relays,
each providing “C” form contacts that can be used for alarm notification.
Each output relay can be configured to report a single alarm, or up to three
alarms in an OR or AND fashion. Output relays 1, 2 and 3 are factory-set and
assigned respectively to Major, Minor and Observation (O1) alarms (see
screen 33), but can be reconfigured and/or reassigned in the field.
Connections to these ports are done on terminal strips, as shown in Figure