Configuring and operating the system
81
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
If it is necessary to modify these thresholds and hysteresis values (at initial
start-up or when replacing the battery by another type, for example), enter the
new values in the fields above the
buttons, then click on the
applicable
button to confirm each of the new values.
When entering new values, make sure that these are within the range
specified below each parameter title in the above screen, and that you observe
the note at the bottom of the second and third boxes.
5.6.5.3. AC Mains Failure Delay
Clicking on
AC Mains Failure Delay
in the submenu screen for system
settings will display the following screen.
Screen 14
This screen is used to set the delay between the time an AC mains failure
occurs and the time the AC mains failure alarm is reported by the system.
If such a delay is required, enter the desired delay in minutes (0 to 60), in the
field above the
button, then click on the
button to confirm the
new value.
5.6.5.4. Low Voltage Disconnect
Clicking on
Low Voltage Disconnect
in the submenu screen for system
settings will display the following screen.