96
Configuring and operating the system
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
•
a “Temperature Compensation Status” box to activate or deactivate the
temperature compensation function, and
•
a “Temperature Compensation Settings” box in which to enter the
temperature compensation settings.
Clicking on the
button in the “Temperature Compensation Status”
box will activate the temperature compensation function. The field and button
text will then change from
to
as
shown in the following screen.
Screen 23
Note 1:
Activating the function does not necessarily mean “run” the
function. Once the function is activated, temperature compensation will
occur only when the temperature varies from the nominal value (typically
25ºC - 77ºF) by the value set in the “Cell Factor” field of screen 22.
Note 2:
The temperature compensation function cannot be activated unless
the battery temperature probe is installed and connected to the power
system (refer to the appropriate section of the installation manual,
IM6C55C). The optional ambient temperature probe is not required for the
operation of the temperature compensation function, but it provides an
ambient temperature alarm (default is 35ºC).
Note 3:
The “Cell Factor” and “Nominal Temperature” should be set
according to the battery manufacturer’s specifications.
If it is necessary to modify the settings in the “Temperature Compensation
Settings” box (at initial start-up or when replacing the battery by another
type, for example), enter the new values in the “Nominal Temperature” and
“Cell Factor” fields, then click on the
button to confirm the new
setting.
DO NOT
modify the “Number of Battery Cells” field.
When entering new values, make sure that these are within the range
specified below each parameter title in the “Temperature Compensation
Settings” box.
Clicking on the
button will deactivate the temperature
compensation function.