Communicating with the System Manager
IP
143
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
•
Verify first that your computer is equipped with a network card.
•
Connect the computer to the System Manager CIP with a crossover
network cable (optional - A7000827); connect one end of the cable to
the network card on the computer, and the other end to the RJ45
Ethernet port on the front panel of the System Manager CIP.
Note:
Direct PC connection into the RS-232 serial port is not possible. To
use the RS-232 serial port, a dial-up line must be used as described below.
6.3.2.
Remote Ethernet connection
To access the RJ45 Ethernet port of the System Manager CIP from a remotely
located PC, proceed as follows:
•
Verify first that your computer is equipped with a network card and
that it is connected to a LAN or WAN network with an Ethernet cable.
•
Ensure that the RJ45 Ethernet port of the System Manager CIP is also
connected to a LAN or WAN network with a straight Ethernet cable.
•
Check that your services, protocols and adapters are correctly installed
and configured. If you are not sure how your computer is to be
installed and configured, contact your network administrator for
advice. The network connection to be used is an ordinary TCP/IP
connection.
•
When accessing the System Manager CIP through a firewall, it is
required to enable the following TCP/IP ports: 80 for the Web browser,
5555 for the remote GUI, and 2121 for software upgrade.
Note:
If Explorer is used for the remote network connection, it is required
to configure the Internet option to “Update every page as loaded” instead
of “Automatic” in Settings, and to frequently do a right click and a Refresh
in order to update the displayed page. This is not required if Netscape is
used.
6.3.3.
Remote dial-up connection
CAUTION
Protection the equipment against damages
Before connecting a modem cable into the RS-232 connector
of the System Manager CIP, ensure that the frame ground
and/or BRR cable for the system is/are connected.
To access the RS-232 serial port of the System Manager CIP from a remotely
located PC, proceed as follows:
•
Verify first that your computer is equipped with a modem that is
connected to a regular dial-up line.
•
Ensure that an external modem (optional) is connected to the RS-232
serial port of the System Manager CIP and to a regular dial-up line.