When this function is activated, the INHIB button will have changed to
ACTIV. To reactivate the output alarm relays, press the ACTIV button. You
will be asked to confirm that you want to reactivate the output alarm relays.
Reactivate the output alarm relays pressing the YES button, or maintain the
inhibit command by pressing the NO button.
If the inhibit command is not cancelled, the system will return to “Alarms on”
after 24 hours. While the output alarm relays are inhibited, the system sends
out a service an alarm through the O1 output relay.
Note:
When the output relays are inhibited, all alarms are still displayed on
the local screen, as well as on the remote GUI.
5.5.8.2. Clear Active Alarms
This submenu is used to clear the “Bad Battery” and “Battery Test Fail”
alarms. Use the
and
buttons to select which alarm is to be cleared, then
press the CLEAR button. You will be asked to confirm that you want to clear
the alarm. Clear it by pressing the YES button, or maintain it by pressing the
NO button.
5.5.8.3. Clear Battery Test Log
This submenu is used to clear the battery test log. To clear the log, press the
CLEAR button. You will be asked to confirm that you want to clear the log.
Clear it by pressing the YES button, or maintain it by pressing the NO button.
5.5.8.4. Erase Alarm History
This submenu is used to erase the alarm history (log). To erase the alarm
history, press the ERASE button. You will be asked to confirm that you want
to erase the alarm history. Erase the alarm history by pressing the YES
button, or maintain it by pressing the NO button.
5.5.8.5. Start Manual Voltage Boost
This submenu is used to start a voltage boost. To start a voltage boost, press
the START button. You will be asked to confirm that you want to start a
voltage boost. Start a voltage boost by pressing the YES button. The voltage
boost cannot be started if a major (MJ) or minor (MN) alarm is active.
While the batteries are being voltage boosted, the START button in the
Voltage Boost menu will have changed to STOP. To stop the voltage boost,
press the STOP button, and the YES button in the next screen, or wait until
the voltage boost is completed.
Voltage boost is used to reduce the charging time after an AC mains failure
and to equalize the charge level of the batteries.
5.5.8.6. Start Manual Battery Test
This submenu is used to start a battery test. To start the test, press the START
button. You will be asked to confirm that you want to start the test. Start the
battery test by pressing the YES button. The battery test cannot be started if a
major (MJ) or minor (MN) alarm is active alarm is active.