Wire Restrictions
Echelon Network and Hardware Setup
•
8
-
3
8.4.1
Using a Termination Block
(P/N 535-2715) to Terminate a Daisy
Chain
Some Echelon Network devices, notably TD3s, have
no on-board means of terminating. For some other
devices, it is inconvenient to use the jumpers supplied for
termination (the CC-100/CS-100 case controllers, for
example, require the enclosure to be removed to set the
jumper).
To remedy these problems, Emerson Retail Solutions
supplies termination blocks that can be wired to the end of
an Echelon cable segment. This termination block uses the
same three-pin connector as all other Echelon devices.
Wire the two signal wires to the outside terminals, and
connect the shield to the middle terminal (see
Figure 8-4
).
NOTE: The recommended termination proce-
dure for all Echelon devices is the termination
block.
Figure 8-4
- Placement and Wiring of the Termination Block
8.5
Wire Restrictions
Maximum Total Segment Length
The total amount of wire used to connect all E2s and
associated controllers in a single segment (not including
devices on the other side of routers) cannot be longer than
4592 feet (1400 meters). If the total length of cable used is
longer than 4592 feet, a repeater or router will be required.
Routers
act as communication gateways that reduce
the amount of network traffic. They are used when net-
works exceed their 63-node limit. Adding a router allows
you to add another daisy-chain segment of 4592 feet with
a maximum of 63 more nodes.
Repeaters
boost signal strength and are only used in
instances where a segment of 63 nodes or less uses more
than 4592 feet of Echelon cable.
Refer to the
Router and Repeater Installation Guide
(P/N 026-1605)
, for information about router and repeater
placement.
8.6
Installing Echelon
Devices
The E2 control system has several types of peripheral
control boards that communicate using the Echelon Net-
work: the 16AIe analog input board, the 8ROe relay out-
put board, the CC-100/CS-100 series of case control and
case circuit control boards, and the ESR8 board.
8.6.1
Powering Echelon Devices
CAUTION: Do not power Echelon devices
with the same 56VA and 80VA transformers
used to power the I/O Network. Echelon
devices require Class 2 power to operate, which is not
supplied by the I/O board transformers.
All Echelon devices require 24VAC Class 2 power.
Emerson Retail Solutions specs several sizes of transform-
ers to accommodate the full range of Emerson Retail Solu-
tions’ Echelon-compatible products.
Table 8-3
lists each
transformer’s part number and rating.
Table 8-3
- Class 2 Transformers for Echelon Devices
Xformer P/N
VA Rating
Input Voltage
640-0039
10 VA
110 VAC
640-0041
50 VA
110 VAC
640-0042
50 VA
220 VAC
640-0050
75 VA
110 VAC
640-0045
75 VA
220 VAC
To select a power transformer for one or more Echelon
devices:
1.
Determine what the total VA is for the boards
and controllers that will be powered by the
transformer (see
Table 8-4)
.
Example: Two TD3 boards (4 VA each), and
one E2 (40 VA) board are to be powered by
one transformer. The total VA is:
Summary of Contents for E2
Page 2: ......
Page 4: ......
Page 16: ......
Page 24: ......
Page 48: ......
Page 55: ......
Page 56: ......
Page 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Page 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Page 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 81: ......
Page 82: ......
Page 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 114: ......
Page 144: ......
Page 203: ......
Page 204: ......
Page 226: ......
Page 253: ......
Page 254: ......
Page 257: ......
Page 258: ......
Page 267: ......
Page 268: ......
Page 270: ......
Page 282: ......