The 16AI, 8IO, and MultiFlex Inputs
Input and Output Setup
•
9
-
3
P/N
Sensor
Input Type
Dip Switch
Wiring
various
Temp Sensors
and Probes
Up
1.
Connect one lead to the odd
numbered terminal and the
other lead to the even num-
bered terminal (polarity
insensitive).
various
Digital Sensors
(Klixons, Sail
Switches, etc.)
Up
1.
Connect one lead to the odd numbered
terminal and the other lead to the even
numbered terminal (polarity insensitive).
800-2100
800-2200
800-2500
Pressure Trans-
ducers (Emer-
son Retail
Solutions) 100,
200, 500 lb. rat-
ings
(0.5-4.5VDC
output, 5VDC
input voltage)
Up
1.
Connect RED power
wire to +5VDC sup-
ply on input board.
2.
Connect WHITE sig-
nal wire to even num-
bered terminal.
3.
Connect BLACK
ground wire to odd
numbered terminal.
4.
Connect the bare
SHIELD wire to odd
numbered terminal.
203-5750
Relative Humid-
ity Sensor
Down
1.
Wire the “P”
sensor terminal
to 12VDC sup-
ply on board.
2.
Wire the
“GND” sensor
terminal to odd
numbered ter-
minal.
3.
Wire the
“OUT” sensor
terminal to even
numbered ter-
minal.
4.
Jumper sensor
terminal “N” to
sensor terminal
“GND”.
Table 9-1
- Sensor Wiring
Summary of Contents for E2
Page 2: ......
Page 4: ......
Page 16: ......
Page 24: ......
Page 48: ......
Page 55: ......
Page 56: ......
Page 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Page 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Page 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 81: ......
Page 82: ......
Page 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 114: ......
Page 144: ......
Page 203: ......
Page 204: ......
Page 226: ......
Page 253: ......
Page 254: ......
Page 257: ......
Page 258: ......
Page 267: ......
Page 268: ......
Page 270: ......
Page 282: ......