Figure 11-1
- Diagram of a Suction Group
SUCTION
PRESSURE
CO
N
D
E
N
S
E
R
DISCHARGE
PRESSURE
LIQUID RECEIVER
CASE CIRC
UIT
OIL
PRESSURE
CIRCUIT
CASE TEMP
(FOR FLOATING)
LIQUID LINE
SOLENOID
26507005
D
D
D
OIL RESET SWITCHES
Table 11-1 - Suction Group Inputs
Input
Sensor Type
Wiring
Instructions
Suction Pres-
sure
100 lb. Eclipse
transducer
see Table 9-1 on
page 9-3.
Discharge Pres-
sure
500 lb. Eclipse
transducer
see Table 9-1 on
page 9-3
Oil Pressure
200 lb. Eclipse
transducer
see Table 9-1 on
page 9-3
Case Circuit
Temperature
Temperature
see Table 9-1 on
page 9-3
Oil Reset
Switches
Digital
see Table 9-1 on
page 9-3
Table 11-2 - Suction Group Outputs
Output Device
Wire Output Board
Contacts to:
Set Failsafe Dip
Switch to:
Notes
Compressor
N.C.
N.C. (up)
If you want a compressor to be OFF during network/
power loss, use N.O. failsafes instead.
Unloader
N.C.
N.O. (down)
These fail-safe settings are specifically for unloaders.
Liquid Line Sole-
noid (LLS)
N.C.
N.C. (up)
Keeps solenoid energized during network/power loss.
Electric Defrost
N.O.
N.O. (down)
Keeps contacts de-energized during network/power loss.
Condenser Control
Software Overview
•
11
-
3
11.2 Condenser Control
An E2 RX is capable of controlling air-cooled or evap-
orative condensers. The E2 RX-300 may control a single
condenser, while the RX-400 may control up to two con-
densers.
11.2.1 Air Cooled Condensers
An air-cooled condenser consists of one or more fans
that blow air across a manifold of tubing to cool heated
refrigerant and condense it into a liquid. The E2 controls
condensers by activating or deactivating fans in order to
maintain discharge pressure or temperature at or below a
chosen setpoint.
A Condenser Control application may use either of two
strategies to operate air cooled condensers: an air-cooled
strategy, or a temperature differential (T-D) strategy.
11.2.1.1 Air Cooled Strategy
The air cooled strategy uses a simple PID control loop
that compares a single Control In input to a PID setpoint.
The resulting percentage is used to activate the condenser
fan(s) necessary to bring the input value down below the
setpoint.
Control inputs for air cooled strategies most commonly
come from a pressure transducer mounted on either the
discharge line, the condenser inlet, or the condenser outlet.
However, temperature sensor values will also be accepted.
11.2.1.2 Temperature Differential
Strategy
The temperature differential strategy attempts to keep
a minimum amount of difference between the temperature
of the refrigerant and the ambient outside temperature.
This strategy begins by determining the temperature of
the refrigerant coming into the condenser. This can be sup-
plied by either a temperature sensor or pressure transducer
located near the condenser inlet; if it’s a pressure trans-
ducer, its value will automatically be converted to a tem-
perature value based upon the type of refrigerant.
Summary of Contents for E2
Page 2: ......
Page 4: ......
Page 16: ......
Page 24: ......
Page 48: ......
Page 55: ......
Page 56: ......
Page 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Page 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Page 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 81: ......
Page 82: ......
Page 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 114: ......
Page 144: ......
Page 203: ......
Page 204: ......
Page 226: ......
Page 253: ......
Page 254: ......
Page 257: ......
Page 258: ......
Page 267: ......
Page 268: ......
Page 270: ......
Page 282: ......