Table 11-11 - Suction Group Outputs
Output Device
Wire 8RO contacts
to:
Set Fail-safe Dip
Switch to:
Notes
Heat / Cool
Staged Outputs
see note
see note
Set up any stages you want ON when the controller is off-
line as N.C. Stages you want OFF should be set as N.O.
Single-Speed
Fans
see note
see note
If one or more heat or cool stages will be ON, wire fan
N.C. so it will be active during controller off-line times.
Otherwise, wire N.O.
Two-Speed Fans
(LOW, HIGH,
and fan contac-
tor)
see note
see note
If any heat or cool stages are configured to be ON (N.C.),
set the wiring and the switch to N.C., and set either the
LOW or HIGH stage output to N.C. (whichever speed
you want active). If no heat or cool will be active, set
LOW, HIGH, and the fan contactor to N.O.
Digital Econo-
mizer
N.O.
N.O.
Zone Control
Software Overview
•
11
-
25
11.7 Zone Control
11.7.1 Overview
An
HVAC Zone
is a collection of up to sixteen rooftop
units or air handling units that work together to maintain
the same temperature and humidity throughout a particular
volume of space. The primary function of an HVAC Zone
is to “manage” the operation of each individual HVAC
unit by providing the temperature setpoints that will be
used in Temperature Control. Zones are also responsible
for ordering HVAC units to dehumidify and determining
when outside air conditions are favorable to economize.
11.7.2 How Zones Work
A Zone is built by first creating a Zone application in
the E2 BX. Then, all HVAC unit applications that will be a
part of the Zone must be connected with the Zone applica-
tion. This connection process is known as
association
.
When a rooftop unit or AHU is associated with a Zone,
the E2 automatically makes a series of I/O connections
between the Zone application and the individual MultiFlex
RTU or AHU application. From that point on, the Zone is
responsible for passing along the following information to
the individual unit:
• The heating and cooling setpoints it will use
during occupied and unoccupied building
times.
• A command to operate in either occupied or
unoccupied mode (based on the Zone appli-
cation’s own time schedule input).
• Outdoor air and outdoor relative humidity
values.
• A signal to enable or disable economization
(based on the Zone application’s own econo-
mization checking method).
• A signal to begin or end dehumidification
(based on the Zone application’s own humid-
ity reading and dehumidification setpoint).
• A signal indicating the current season is
either SUMMER or WINTER.
• The combined Zone Temperature and Zone
humidity (based on a combination of each
HVAC unit’s space temperature and space
humidity).
• The fallback temperature and humidity set-
points to use in case the unit loses contact
with its Zone application.
Summary of Contents for E2
Page 2: ......
Page 4: ......
Page 16: ......
Page 24: ......
Page 48: ......
Page 55: ......
Page 56: ......
Page 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Page 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Page 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 81: ......
Page 82: ......
Page 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 114: ......
Page 144: ......
Page 203: ......
Page 204: ......
Page 226: ......
Page 253: ......
Page 254: ......
Page 257: ......
Page 258: ......
Page 267: ......
Page 268: ......
Page 270: ......
Page 282: ......