C-6
•
E2 RX/BX/CX I&O Manual
026-1614 Rev 4 5-JAN-2013
External Fault
30
An external fault input defined in a Multiflex PAK
controller has indicated a failure. External fault
inputs in the PAK are used to detect a Rack (Pack)
failure produced by some device out of the PAK's
control.
Failed Attempt To Bind Input
50
A valid link could not be made between an E2 appli-
cation and an input assigned to it.
Failed Sensor Or Bad Wiring
20
E2 is unable to get a valid sensor value due to a possi-
ble hardware problem.
Failed To Create logging
20
E2 is unable to create logs for the input or output
shown.
Failed to Obtain DHCP Lease
20
Failed to obtain a DHCP lease from the DHCP
Server, when a lease is requested. This happens at
system startup, if a DHCP lease is requested, or if the
user switches to using DHCP.
Failed to Renew DHCP Lease
20
DHCP Lease failed to renew altogether. DHCP
Leases are renewed at an interval of half the time of
the requested lease. If the lease is for 5 days, then a
renewal will happen at 2.5 days. If this fails, it will
retry at the ¾ of the lease time. If both attempts fail,
the alarm is generated.
Fax Init String Is Not Valid
30
The fax initialization string for the E2’s modem is
incorrect and may need editing.
Features denied during restore
99
License manager has denied permission to access a
feature during a restore. Either the license for that
feature is invalid or it does not exist, or the number of
licenses for that feature is less than the number
needed for the configuration. Further information
may be found in the service log.
Features denied during startup
99
License manager denied permission to access a fea-
ture during startup. Either the license for that feature
is invalid or it does not exist, or the number of
licenses for that feature is less than the number
needed for the configuration. Further information
may be found in the service log.
File Not Found
50
An internal error has occurred in the E2.
Firmware File Bad - AI200
15
A 16AIe has corrupted firmware.
Firmware File Bad - RO200
15
An 8ROe has corrupted firmware.
Firmware File Bad - CC100 Liq
15
A CC-100P or CC-100LS has corrupted firmware.
Firmware File Bad - CC100 Suct
15
A CC-100H has corrupted firmware.
Firmware File Bad - CS100 Ckt
15
A CS-100 has corrupted firmware.
Firmware File Bad - ESR8
15
An ESR8 has corrupted firmware.
Firmware File Bad - RT100
15
An RT-100 has corrupted firmware.
Alarm Name
Default
Priority
Definition
Summary of Contents for E2
Page 2: ......
Page 4: ......
Page 16: ......
Page 24: ......
Page 48: ......
Page 55: ......
Page 56: ......
Page 72: ...6 16 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 75: ...BACnet The RS485 Network and Hardware Setup 6 19 ...
Page 79: ...BACnet The RS485 Network and Hardware Setup 6 23 ...
Page 80: ...6 24 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 81: ......
Page 82: ......
Page 92: ...8 6 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 94: ...8 8 E2 RX BX CX I O Manual 026 1614 Rev 4 5 JAN 2013 ...
Page 114: ......
Page 144: ......
Page 203: ......
Page 204: ......
Page 226: ......
Page 253: ......
Page 254: ......
Page 257: ......
Page 258: ......
Page 267: ......
Page 268: ......
Page 270: ......
Page 282: ......