1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
121/192
Reset
Digital input not active
Restart
Manual (reset procedure in function menu)
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Sanitay heaters OFF
Atr1 REMOTE TERMINAL 1 (VICX620) COMMUNICATION ALARM
Label on alarm
visualization menu
Atr1 (communication alarm with remote terminal 1)
Atr2 (communication alarm with remote terminal 1)
Origin
Absence of serial communication with remote keyboard n°1
Reset
When the serial communication works properly
Restart
Automatic
Symbol
blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
OFF it the remote terminal has internal probe and it is the regulation probe
AtSF: supply fan overload alarm
Label on alarm
visualization menu
AtSF:
Overload alarm of the supply fan
Origin
CF01=0: After on fan when the ID is activated for AL15 time. After on pump
when the ID is activated for AL17.
Reset
Digital input not active for AL18 time
Restart
Automatic
– Manual if the digital input is active for AL16 seconds (Reset
procedure in Menu function).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
MANUAL RESET OF THE OVERLOAD ALARM OF THE SUPPLY FAN
If the digital input is active for AL16 seconds it is necessary to restart manually the unit (reset procedure in
larm Menu with blinking label
Reset
if the alarm is not active from Al18 otherwise label
Active
(can not be
reset)). Push SET key to reset the alarm, the label disappears, the fan restarts and the alarm is by-passed
for AL15 time delay to allow the start-up if within this interval the alarm does not appear again.
AUAL Failed Communication With Electronic Expansion Valve
Label on alarm
visualization menu
AUAL
Origin
Failed communication with electronic expansion valve
Reset
Automatic when the communication is working
Restart
Automatic
Symbol
blinking
Action
Alarm relay + buzzer ON
Regolatori
Loads
OFF
AtrE: REMOTE TERMINAL VISOGRAPH 2.0 COMMUNICATION ALARM
Label on alarm
visualization menu
AtrE
Origin
Absence of serial communication with remote keyboard Visograph 2.0
Reset
When the serial communication works properly