1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
111/192
ACF1 …AC15: Configuration alarm
Label on alarm
visualization menu
ACF1
Heat pump unit but 4-way valve not configured
Wrong configuration of defrost parameters dF22 and dF23
Defrost only with condenser fan enabled but external temperature probe
not configured
ACF2
Condenser fan configured as step or proportional control, but condenser
probes not configured
Condenser fan configured for proportional control and following rules not
respected:
FA09 + FA11 + FA12 < FA10
FA12 < FA13
FA07 < FA15 < FA08
FA18 + FA21 + FA20 < FA19
FA21 < FA22
FA16 < FA23 < FA17
Condenser fan configured for ON/OFF control and following rules not
respected:
FA09 < FA10
FA18 < FA19
If the defrost is enabled and:
-
no evaporating/condensing probes is configured
-
dF18 > FA35
-
FA34 < FA07
-
FA34 > FA08
-
FA07<FA34<FA08
-
dF18<FA10
•
In two circuits unit and two separated condenser, two condenser probe are
not configured
If condenser fan is configured with modulation and PWM outoput, and the
power supply selection is dc voltage (CF63 = 2)
If condenser fan is enabled as step control, the following rules are to be
respected:
FA09 < FA10 < FA26 < FA27 in cooling mode
FA29 < FA28 < FA19 < FA18 in heating mode
ACF3
Two relays, or two digital inputs, or two probes are configured with the
same function or without the necessary resources (es. compressor 3
overload alarm but compressor 3 relay not configured)
ACF4
Heating / Cooling selection
CF59=1 and none digital input configured as Chiller request or Heat Pump
request
CF59=2 and none probe configured as external temperature probe
Unit configured as Heat pump and rack compressor unit enabled (Cr01>0)
CF03 = 1 (condensing unit enabled) and wrong configuration of the digital
input or digital output for condensing unit
ACF5
Circuit 2 not configured but at least one of its resources are configured (e.g.:
solenoid pump-down valve, heaters, inversion valve, fan, recovery, etc)