Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL44
Restart
Automatic
– It becomes manual after AL42 events/hour
Logged only if manuale
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
REGULATION
Alarm
Alarm relay + buzzer ON
Other loads
OFF
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded.
ALC2: Generic Signal alarm
Label on alarm
visualization menu
ALC1:
generic signal alarm from digital input
if AL50 = 0
Origin
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL52
Reset
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL53
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
REGULATION
Alarm
Alarm relay + buzzer ON
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ALC2: Generic alarm with stop regulation
Label on alarm
visualization menu
ALC1:
generic signal alarm from digital input with stop regulation
if AL50 = 1
Origin
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL52
Reset
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL53
Restart
Automatic
– It becomes manual after AL51 events/hour
Logged only if manuale
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
REGULATION
Alarm
Alarm relay + buzzer ON
Other loads
OFF
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ALSF: Phase sequence alarm
Label on alarm
visualization menu
ALSF
Origin
Digital input active
Reset
Digital input not active
Restart
Automatic