1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
118/192
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
ALti: low air ambient temperature (Air / Air unit only)
Label on alarm
visualization menu
ALti
(low temperature value of the evaporator air inlet)
Origin
Chiller mode: evaporator inlet NTC probe lower than AL26 for AL28 seconds.
Heat pump: evaporator inlet NTC probe lower than lower than AL33 forAL36
seconds
In stand-by or remote OFF: evaporator inlet NTC probe lower than the lowest
value compared between AL28 and AL36.
Reset
Chiller: evaporator inlet NTC probe higher than AL26 + AL27(differential).
Heat pump: evaporator inlet NTC probe higher than AL33 + AL34 (differential).
n stand-by or remote OFF: the evaporator inlet NTC probe higher than
AL26+AL27 or AL33+AL34.
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
AP1 ... AP8, APr1.. Apr2, APE1 .. APE8, APU1 .. APU4 PROBE FAILURE
Label on alarm
visualization menu
AP1
= PB1 probe alarm…
AP6
= PB6 regulator probe alarm
APr1
= remote keyboard 1 alarm probe …
APr2
= remote keyboard 2 alarm
probe
APE1
I/O expansion probe 1 alarm…
APE8
I/O expansion probe 8 alarm
APU1
expansion valve probe 1 alarm...
APU4
expansion valve probe 2 alarm
Reason
Probe configured but the read-out is not in the range
Reset
Probe not configured or probe in the right range
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
Loads
The behaviour of the load depend on witch probe is on error (regulation probe
= all loads OFF; external temperature probe = only loads involved on this
probe)
APFL: solar panel flow alarm
Label on alarm
visualization menu
APFL solar panel flow alarm
Origin
The flow switch alarm is not detecded for AL69 seconds starting from water
pump activation.
Flow switch alarm is signalled if the digital input is active for AL71 seconds.
Reset
Automatic reset: digital input not active for AL72 seconds.
Manual reset: Reset procedure in Menu function
Type of alarm
Automatic if flow switch digital input activation < AL70 + AL71
Manual if Automatic if flow switch digital input activation > AL70 + AL71
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
Loads
Solar panel water pump OFF
ArtC Clock alarm