IC200D
14/192
4. Select the
UPL
function (on the bottom display)
5.
Push
SET
key and immediately the instrument starts transfer the parameters into the Hot key.
During the upload the regulation is locked and the top display shows the “
UPL
” blinking label. At the end of
the UPLOAD will appear:
“End”
if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err”
if the programming procedure has found an error and the parameter have not been transferred.
Repeat the procedure.
To exit the UPL function push the MENU key or wait the time-out (15 sec).
6.2 PROGRAMMING USING THE KEYBOARD
Through the instrument keyboard it is possible to enter the programming. In all the three accessible levels
the user can show and modify both value and visibility of the parameters. To ensure an easy navigation
through the different levels the common parameters have been named and grouped under a family name.
The three levels of programming:
Pr1 User level
Pr2 Maintenance level
Pr3 OEM level
Password default values
6.2.1
Password level Pr1 =
1
Password level Pr2 =
2
Password level Pr3 =
3
Each password can be changed; the range is 0 ... 999.
Each parameter has two level: visibility and changeability. Therefore it can be configured as follow:
The parameter can be showed and changed.
The parameter can be showed but not changed.
Enter the Pr1 - Pr2 - Pr3 programming levels
6.2.2
Pr1 LEVEL:
Push
SET
+
DOWN
together for 3 seconds, the top display shows the PAS label and the bottom display
shows the Pr1 label. The leds cir1/cir2 are blinking (up and down leds) to inform that you now are in PR1
programming level.
Pr2 LEVEL:
From the Pr1 level push the UP key for 2 seconds and the bottom display will show Pr2. The top display still
shows PAS.
Pr3 LEVEL:
From the Pr2 level push the UP key for 2 seconds and the bottom display will show Pr3. The top display still
shows PAS.
After selecting the level push the SET key and the top display will show the 0 blinking value where to insert
the password .
Set the password level using the UP and DOWN keys then confirm with SET key.
Dependening on the password value there will be the different level access, if the password is wrong the
instrument shows the password value again.
ATTENTION:
For all the programming levels Pr1, Pr2, Pr3 CF parametrs (configuration parameters) cannot be
changed if the instrument is switched on.
During the defrost the dF parameter
s can’t be programmed.
Enter the programming level Pr1
6.2.3
Enter Pr1 “User level ”:
1. Push
SET
+
DOWN
keys together for 3 seconds. The top display shows PAS while the bottom display
shows
Pr1
labels.
2. Push
SET
key and the top display shows a blinking
0
; pressing
UP
or
DOWN keys
insert the Pr1
password. Push
SET
and, if the value is correct, top display will show the first family of parameters
“ALL”
. Otherwise set the password again.
3. Select a parameter group pressing
DOWN
or
UP
keys.