1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
135/192
21 Temperature probe
NTC
for combined defrost circuit 2
22 Temperature probe
NTC
for auxiliary output 1
23 Temperature probe
NTC
for auxiliary output 2
24 Temperature probe
NTC
domestic hot water 1
25 Temperature probe
NTC
domestic hot water 2
26 Temperature probe
NTC
solar panel
27 Temperature probe
NTC
recovery function
28 Condenser probe circuit 1 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
29 Condenser probe circuit 2 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
30 Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
31 Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
32 Aux 1 output probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt)
33 Aux 2 output probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt)
34 Dynamic setpoint probe (
4÷20 mA)
35 Compressor 1 or circuit 1 pressure probe
36 Compressor 2 or circuit 2 pressure probe
After the number 35 the display read-
out goes from “
o 1”
to “
c75
that allows to set an analogue input as
digital input (see polarity input of digital inputs).
48.3 DIGITAL INPUT ID1
– ID9
0. Not enabled
1. Remote ON / OFF
2. Remote chiller / heat pump
3. Flow switch/ Supply fan overload
4. Flow switch of heated side
5. Antifreeze heater circuit 1
6. Antifreeze heater circuit 2
7. High pressure switch circuit 1
8. High pressure switch circuit 2
9. Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 3 high pressure
14. Compressor 4 high pressure
15. Compressor 5 high pressure
16. Compressor 6 high pressure
17. Compressor 1 overload
18. Compressor 2 overload
19. Compressor 3 overload
20. Compressor 4 overload
21. Compressor 5 overload
22. Compressor 6 overload
23. Condenser fan overload of circuit 1
24. Condenser fan overload of circuit 2
25. Condenser fan overload of circuit 1 and 2 (comun)
26. Water pump overload of evaporator 1
27. Water support pump overload of evaporator
28. Water pump overload of condenser 1
29. Water support pump overload of condenser
30. Recovery request circuit 1
31. Recovery request circuit 2
32. Start/End defrost circuit 1
33. Start/End defrost circuit 2
34. Energy Saving
35. Pressure switch / compressor 1 oil
36. Pressure switch / compressor 2 oil
37. Pressure switch / compressor 3 oil
38. Pressure switch / compressor 4 oil
39. Pressure switch / compressor 5 oil
40. Pressure switch / compressor 6 oil
41. Pump down pressure switch of circuit 1