1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
169/192
51.2 HARDWARE RESOURCES FOR IC207D MODEL
7 x digital outputs (relays):
MAX current on the relay contacts relè 5(2)A 250V
MAX common current 10A 250V
9 x digital inputs:
(free of voltage)
8 analogue inputs:
5 x NTC preobe / PTC probe / digital input
3 x NTC preobe / PTC probe / digital input / pressure transducer 4÷20 mA / pressure transducer
ratio-metric 0÷ 5.0 Volt
4 x modulating outputs:
1 x 0 ÷ 10 Volt
2 x 0 ÷ 10.0 Volt or PWM (for modulating condenser fan)
1 x output to connect a remote keyboard (max 2 remote keyboards)
1 x LAN to connect an I/O expansion module (ICX207D)
1 x TTL
output for “HotKey 64” (for parameters programming) or for XJ485CX (interface module for
monitoring system)
1 x RS485 output to connect the instrument to a RS485 network (monitoring system) or XWEB
system.
MAX current of relay contacts 5(2)A 250V
MAX current of common line of the relay 10A 250V