1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
113/192
Label on alarm
visualization menu
ACF9
Recovery function enabled but whitout resources needed (heat recovery probe
or digital input, heat recovery valve, condenser probe)
AC10
Compressor inverter controlled
2 anologue output configured to control the same compressor
One analog output is configured to control a compressor via inverter but
none relays is configured as compressor
If the unit is configured as condensing unit and a compressor is
configured as compressor inverter controlled
AC11
Compressor with different power capacity enabled and:
One analog output is configured as output for compressor inverter
controlled
one of the compressor has capacity power = 0
the regulation is not a neutral zone
the compressor is configured with capacity step
AC12
Free cooling function enabled and:
None relay is configured as free cooling
FS41 and FS42 select a probe not configured in CF parameters
If FS21 < FS22
If FS01=2 and CF97=2
If it is not respected the following condition:
FS38 < St07 <= FS37
AC13
Domestic hot water function enabled and:
None relay is configured as valve 1
None probe is configured as probe 1 of domestic hot water
Valves mounted on water circuit and valves configured to be switched
off in STD-BY or OFF
Domestic hot water priority defined by digital input and none digital input
configured for this function
FS49=1 and the regulation is in neutral zone
AC15
Hybrid exchangers enabled and:
dF27-dF29> dF28-dF30
or
dF27>dF28
or
dF32+dF34> dF31+dF33
or
dF32>dF31
Origin
Wrong programming
Reset
Correctly programming
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
ACFL: condenser flow alarm (differential Pressure switch)
Label on alarm
visualization menu
ACFL
condenser flow alarm