1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
18/192
TO SET THE ORIGINAL TAG FOR THE PARAMETER Pr1 / Pr2
1.
Keep pushed the
SET
key;
2.
Push one time the
MENU
key, the leds 3 / 4 turn on, the parameter can be seen and modified in Pr1 and Pr2.
Programming: digital input and output polarity
6.2.11
The configuration parameters of :
Digital inputs
Digital outputs (relay)
Proportional output configured as ON/OFF
Analogue input configured as digital input
are composed by a letter and a number.
Letter can be:
o (open) = function associated to the input or output is active when the contact is open
c (close) = function associated to the input or output is active when the contact is closed
The number defines the function associated to the input or output.
Example 1:
The bottom display shows the parameter label CF36 = digital input 7 configuration:
7
means that the digital input is configured as
“high pressure switch of circuit 1” (see digital input
configuration)
o
means that the digital input is active for
open
contact, then the high pressure alarm is detected
when the digital input is open.