1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
19/192
7.
DISPLAY LAYOUT
Pushing
or
key it is possible to read the valure of the probes connected to the instrument.
Every probe is identified by a label (see display visualization table).
Example:
Fig.1
: upper display shows outlet 1 evaporator temperature, the lower display shows Out1.
Pressing SET key is possible to read the same probe of the second circuit (if configured).
Fig.1
Fig.2
: upper display shows outlet 2 evaporator temperature, the lower display shows Out2.
Pressing SET key is possible to read the same probe of the first circuit.
Fig.2
8.
SET POINT VISUALIZATION
8.1 READ SET POINT VALUE
Push and release the
SET
key, the leds of the circuits are off and the set value is displayed.
In stand-by the bottom display shows
SetC
(set chiller), by pushing SET again the next label is
SetH
(set
heat pump ).
If the unit is running the only set displayed is related to the running mode.
8.2 MODIFY THE SET POINT
1) Push
SET
key for at least
3
seconds: the leds of the circuits are off and the set value is blinking.
2) Use the
UP
or
DOWN
key to modify the setpoint.
3) Push
SET
to confirm or wait the timeout (15seconds).