1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
21/192
9.1 ALARM LIST: READ AND RESET
ALrM FUNCTION
Enter the function MENU pushing M key one time
1) Use the
UP
or
DOWN
to select the AlrM label
2) Push
SET
key (Nothing happens if there are no active alarm events)
3) Bottom display: alarm label code; Top display: label
rSt
to reset or
NO
if it is not possible.
4) Use the
UP
or
DOWN
to scroll the alarm list.
5) Pushing SET when the rSt label is displayed the corresponding alarm is reset
6) Then the display shows next alarm in the list; pushing SET again the alarm is reset and the display
shows next alarm etc.
7) Nothing happens by pushing SET when the label NO is displayed, in this case push UP or DOWN to
move to another alarm label.
8) To exit the ALrM reset function push MENU one time or wait the timeout.
MANUAL ALARM RESET IF PASSWORD IS REQUESTED
Enter Menu function
1. Use UP or DOWN key and select the alarm label on the bottom display.
2. Push
SET
one time, if there are active alarms the bottom display shows the alarm label (e.g.
CO1r
for
overload compressor 1) while the top display shows the label
rSt
to reset the alarm or
NO
if the alarm
can not be reset. Use the UP or DOWN keys to scroll all the alrm list.
3. Nothing happens by pushing SET when the label NO is displayed.
4. Pushing SET when the rSt label is displayed the corresponding alarm will be reset after the password:
bottom display ArSt while the top display PAS.
5. Push SET and the top display blinks 0 while the bottom shows
PAS
. Insert the password using UP or
DOWN key. If the password is OK the
ArSt
blinks for per 3 seconds, if the password value is not correct
the top display blinks 0 while the bottom shows PAS. If within 5 seconds no value is inserted the display
label come back to CO1r function.
6. To exit the COtr function push MENU or wait the timeout.
7. Repeat operation 1
– 5 to reset the other alarms.
By parameters AL 97 and AL 98, you can make sure that, after resetting a number of alarms with manual
reset, the password is required to gain access to the menu ALARM:
• If AL97 and AL98 = 0 = 0 no password is required to access the alarm menu
• If AL97 = 1 is always prompted for a password to access the alarm menu
• If AL97 and AL98 = 0> 0 can access the alarm menu until the number of alarms is lower than AL98 reset
manually, after which you must enter the password
COMPRESSOR OVERLOAD PASSWORD
The parameter that define the password is AL46; default value is
4.
9.2 ALARM LOG LIST
ALOG FUNCTION TO SEE THE ALARM LOG
The function and the alarm codes are visible only if there are alarm events. If many events are active at the
same time the list displayed by increasing order.
Enter the function Menu
1. Select
ALOG
2. Push
SET
one time; nothing happens if there are no active alarm.
3. The bottom display shows the alarm label, the top display shows the a number in the range 00 to 99.
4. Use the UP or DOWN keys to scroll the list.
5. To exit the ALOG function push MENU or wait the timeout.
9.3 ERASE THE ALARM LOG LIST
ALOG FUNCTION TO ERASE THE LOG LIST
1. Enter the function Menu.
2. Push
UP
or
DOWN
keys to select ALOG on the bottom display.
3. Push
SET
key.
4. Push
UP
or
DOWN
keys to search
ArSt
label on the bottom display.