1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
154/192
CO 91
Minimum time between to switch on of the compressor
0
250
sec
CO 92
Compressor activation delay starting from water solenoid valve activation
0
250
sec
CO 93
Water solenoid valve de-activation delay starting from compressor de-
activation
0
250
sec
CO 94
% output of the inverter compressor in defrost
1
100
%
CO 95
Free cooling water pump operation time to generate maintenance warning
0
999
10 Hr
10 Hr
CO 96
% output of the inverter compressor in unloading
1
100
%
CO 97
Disable condenser water pump with contemporary c domestic hot
water operation
0= water pump enabled
1= water pump disabled
0
1
CO 98
Compressor contemporary operation time for rotation
0
250
sec
CO 99
Enable supply fan / evaporator water pump when condensing unit doesn’t
require compressors activation
0
1
Parameter Description
min
max
M. u.
Resolution
US 1
Auxiliary relay 1 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0
4
US 2
Analog input configuration for auxiliary relay 1 control. Allows to select which
probe value Pb1..Pb10 controls the relay
1
22
US 3
Auxiliary relay 1 summer minimum set point
-50.0
-58
0.0
0
US5
°C
°F
Bar
Psi
Dec
int
Dec
int
US 4
Auxiliary relay 1 summer maximum set point
US5
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 5
Auxiliary relay 1 summer set point
US3
US4
°C
°F
Bar
Psi
Dec
int
Dec
int
US 6
Auxiliary relay 1 winter minimum set point
-50.0
-58
0.0
0
US8
°C
°F
Bar
Psi
Dec
int
Dec
int
US 7
Auxiliary relay 1 winter maximum set point
US8
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 8
Auxiliary relay 1 winter set point
US6
US7
°C
°F
Bar
Psi
Dec
int
Dec
int
US 9
Auxiliary relay 1 summer differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 10
Auxiliary relay 1 winter differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 11
Auxiliary relay 2 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0
4
US 12
Analogue input configuration for auxiliary relay 2 control . Allows to select
which probe value Pb1..Pb10 controls the relay
1
22
US 13
Auxiliary relay 2 summer minimum set point
-50.0
-58
0.0
0
US15
°C
°F
Bar
Psi
Dec
int
Dec
int
US 14
Auxiliary relay 2 summer maximum set point
US15
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 15
Auxiliary relay 2 summer set point
US13 US14
°C
°F
Bar
Psi
Dec
int
Dec
int