Menu 6
92
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Figure 10-16 Low DC bus operation
Low DC bus is only available on Commander SKB, SKC and SKD.
The remote LED display has a function key. When the key is pressed this parameter will be On(1) otherwise it will be OFF(0). This allows drive user
programming to access the function key.
This parameter permanently enables the Stop key on the drive such that the drive will always stop when the stop switch is pressed. If keypad mode is
selected this has no effect because the stop key is automatically enabled.
The sequencer logic has been designed so that pressing the stop key, whether the stop key is enabled or not, does not make the drive change from
a stopped to a running condition. As the stop key is also used to reset trips this means that if the stop key is pressed when the drive is tripped, the trip
will be reset but the drive will not start. This is done as follows.
Sequencer latching not enabled (Pr 6.40 = OFF)
If the stop key is pressed when the stop key is enabled (Pr
6.12
= On) or when the drive is tripped the sequencer run is removed, and so the drive
stops or remains stopped respectively. The sequencer run can only then be reapplied after at least on of the following conditions occurs.
6.11
Remote LED keypad function key status
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
Background
6.12
Enable stop key
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
OFF(0) or On(1)
Default
Eur: OFF(0), USA: On(1)
Update rate
Background
DC
B
us
(VD
C
)
600
200
400
0
NOTE