10.8 Menu 7: Analog inputs and outputs
Table 10-9 Menu 7 parameters: single line descriptions
Parameter
Range
Default
Setting
Update Rate
7.01
Analog input 1 level (terminal T2)
{
94
)
0.0 to 100.0%
5 ms
7.02
Analog input 2 level (terminal T4)
{
95
}
0.0 to 100.0%
5 ms
7.03
Not used
7.04
Heatsink temperature
-128 to 127
°
C
B
7.05
Power circuit temperature 2
-128 to 127
°
C
B
7.06
Analog input 1 mode (terminal T2)
{16}
0 -20(0), 20-0(1), 4-20(2),
20-4(3), 4-.20(4), 20-.4(5),
VoLt(6)
4-.20(4)
B
7.07
Not used
7.08
Analog input 1 scaling
0.000 to 4.000
1.000
B
7.09
Analog input 1 invert
OFF(0) or On(1)
OFF(0)
5 ms
7.10
Analog input 1 destination
Pr
0.00
to Pr
21.51
Pr
1.36
Drive reset
7.11
Analog input 2 mode (terminal T4)
VoLt(0) or dig(1)
VoLt(0)
B
7.12
Analog input 2 scaling
0.000 to 4.000
1.000
B
7.13
Analog input 2 invert
OFF(0) or On(1)
OFF(0)
5 ms
7.14
Analog input 2 destination
Pr
0.00
to Pr
21.51
Pr
1.37
Drive reset
7.15
Not used
7.16
Not used
7.17
Not used
7.18
Not used
7.19
Analog output source
Pr
0.00
to Pr
21.51
Pr
2.01
Drive reset
7.20
Analog output scaling
0.000 to 4.000
1.000
21 ms
7.21
Not used
7.22
Not used
7.23
Not used
7.24
Not used
7.25
Not used
7.26
Not used
7.27
Not used
7.28
Current loop loss indicator
OFF(0) or On(1)
5 ms
7.29
Not used
7.30
Analog input 1 offset
±
100.0%
0.0
5 ms
7.31
Analog input 2 offset
±
100.0%
0.0
5 ms
7.32
Not used
7.33
Analog output control (Terminal B1)
{36}
Fr(0), Ld(1), A(2), Por(3),
USEr(4)
Fr(0)
Edit mode exit
7.34
IGBT junction temperature
±
200
°
C
B
7.35
Drive thermal protection accumulator
0 to 100%
B
7.36
Power circuit temperature 3
-128 to 127
°
C
B
Summary of Contents for 2202