Menu 15
I/O options
182
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Only parameters that are not protected can be controlled by analog inputs. If a non-valid parameter is programmed to the destination of an analog
input, the input is not routed anywhere. After a modification to this parameter, the destination is only changed when a reset is performed.
The parameter required to be represented as an analog signal by the analog output on Terminal T3 should be programmed in this parameter. Only
parameters that are valid can be programmed as a source. If a non-valid parameter is programmed as a source, the output will remain at zero. After
a modification to this parameter, the source is only changed when a reset is performed.
This parameter can be used to scale the analog output if so desired. However in most cases it is not necessary as the output is automatically scaled
such that when the source parameter is at its maximum, the analog output will be at its maximum.
If a Solutions Module error is detected, the drive will trip on SL.Er. The reason for the trip is stored in Pr
15.50
.
Table 10-28 Error Codes
The drive can also trip on a number of Solutions Module trips, SL.xx. Please see table 9-13, Trip Indications in the Commander SK Advanced User
Guide.
The SM-I/O Lite and SM-I/O Timer includes a temperature monitoring circuit. If the pcb temperature exceeds 65
°
C, the drives cooling fan is forced to
operate for a minimum of 20 seconds. If the pcb temperature falls below 65
°
C, the fan will switch off. If the pcb temperature exceeds 70
°
C, the drive
will trip on SL.Er and the error status will be set to 74.
15.43
Analog input 1 destination (Terminal T2)
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
2
1
1
1
1
Range
Pr
0.00
to Pr
21.51
Default
Pr
0.00
Update rate
Drive read on reset
15.44 to 15.47
Unused parameters
15.48
Analog output 1 source (Terminal T3)
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
2
1
1
1
1
Range
Pr
0.00
to Pr
21.51
Default
Pr
0.00
Update rate
Drive read on reset
15.49
Analog output 1 scaling (Terminal T3)
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
3
1
1
1
Range
0.000 to 4.000
Default
1.000
Update rate
Background read
15.50
Solutions Module error status
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
0 to 255
Update rate
Background write
Error Code
Reason for Fault
0
No error
1
Digital output short circuit
2
Current input to high or too low
3
Encoder supply over current
4
SM-I/O Lite / SM-I/O Timer serial communications error
5
Real time clock error (SM-I/O Timer only)
74
SM-I/O Lite / SM-I/O Timer PCB over temperature
Summary of Contents for 2202