Menu 6
100
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Bit 12: Trip drive
When the control word is enabled (Pr
6.43
) bit 12 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) When
bit 12 is set to one a CL.bt trip is initiated. The trip cannot be cleared until the bit is set to zero.
Bit 13: Reset drive
When the control word is enabled (Pr
6.43
) bit 13 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) When
bit 13 is changed from 0 to 1 the drive is reset. This bit does not modify the equivalent parameter (Pr
10.33
).
Bit 14: Keypad watchdog
When the control word is enabled (Pr
6.43
) bit 14 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) A
watchdog is provided for an external keypad or other device where a break in the communication link must be detected. The watchdog system can be
enabled and/or serviced if bit 14 of the control word is changed from zero to one with the control word enabled. Once the watchdog is enabled it must
be serviced at least once every second or an “SCL” trip occurs. The watchdog is disabled when an “SCL” trip occurs, and so it must be re-enabled
when the trip is reset.
0
: OFF Fan controlled by drive
1
: On Fan runs at full speed
When this parameter is set to OFF(0), the fan is controlled by the drive. If the heatsink temperature is 60
o
C or above the drive output current (Pr
4.01
)
is above 75% of the drive rated current or the option is over temperature, the fan will switch on and run at full speed for a minimum of 20s. After 20s,
if the heatsink temperature falls below 60
o
C or the drive output current falls below 75% of the drive rated current, the fan will switch off. If the
temperature remains above 60
o
C or the drive output current remains above 75% of the drive rated current, the fan will continue running at full speed.
When this parameter is set to On(1), the fan runs at full speed at all times when the drive is powered up (Commander SK size B and C).
Refer to Pr
on page 103 for more information on the cooling fan for Commander SK size D and 2 to 6.
6.44
Unused parameter
6.45
Force cooling fan to run at full speed
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
Background