Commander SK Advanced User Guide
5
Issue Number: 9 www.controltechniques.com
2 Parameter x.00
Pr
x.00
(not Pr
0.00
) is available in all menus and has the following functions:
1000
Save parameters
1070
Option reset
2.1 Saving parameters
When parameters are saved, all user save (US) parameters are saved to EEPROM within the drive. Normally Pr
x.00
(not Pr
0.00)
is set to 1000 and
a reset command is given to initiate a parameter save. This can be achieved on the drive by setting Pr
71
to
1.00
, then setting Pr
61
to 1000 and a
reset command to activate a parameter save. When parameter save is complete, Pr
x.00
is reset to zero by the drive. The drive must not be in the
under voltage (UU) condition for a save to take place. Saving parameters can take between 400ms and several seconds depending on the number of
parameter values that are different from the values already saved in EEPROM. If the power is removed from the drive during a parameter save, it is
possible for the EEPROM data to be corrupted giving an EEF failure when the drive is next powered up.
2.2 Loading default parameters
When default parameters are loaded, the new default parameter set is automatically saved to the drive EEPROM.
See Pr
29
in the
Commander SK Getting Started Guide
or Pr
11.43
in this Advanced User Guide.
2.3 Eur/USA parameter set differences
The following table gives the differences between the Eur and USA default parameters sets:
Pr
Description
Eur default
USA default
Voltage rating
1.06
Maximum set speed
50.0Hz
60.0Hz
All
2.08
Standard ramp voltage
750V
775V
400V
2.11
Acceleration rate
5.00/100Hz
33s/100Hz
All
2.21
Deceleration rate
10.0s/100Hz
33s/100Hz
All
5.06
Motor rated frequency
50.0Hz
60.0Hz
All
5.08
Motor rated full load rpm
1500rpm
1800rpm
All
5.09
Motor rated voltage
400V
460V
400V
5.14
Voltage mode select
Ur I
Fd
All
5.15
Low frequency voltage boost
3.0%
1.0%
All
6.04
Start/Stop logic select
0
4
All
6.12
Enable stop key
OFF (0)
On (1)
All
8.22
Terminal B4 digital input destination
Pr
6.29
Pr
6.29
All
8.23
Terminal B5 digital input destination
Pr
6.30
Pr
6.34
All
8.24
Terminal B6 digital input destination
Pr
6.32
Pr
6.31
All
11.27
Drive configuration
AI.AV
PAd
All
21.01
Motor 2 maximum set speed
50.0Hz
60.0Hz
All
21.06
Motor 2 motor rated frequency
50.0Hz
60.0Hz
All
21.08
Motor 2 motor rated full load rpm
1500rpm
1800rpm
All
21.09
Motor 2 motor rated voltage
400V
460V
400V