Menu 2
54
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
These bits are provided for control by logic input terminals for external ramp selection (see Pr
This parameter can select 3 different ramp rates, as follows:
0
: s/1000Hz
1
:
s/100Hz(default)
2
:
s/10Hz
Therefore, for 0 to 50Hz:
0
: Maximum ramp time of 160 seconds, resolution 0.005s
1
: Maximum ramp time of 1600 seconds, resolution 0.05s
2
: Maximum ramp time of 16000 seconds (>4 hours), resolution 0.5s
Example:
If Pr
2.11
Acceleration rate 1
is set to 10, the following acceleration time would apply according to the value of Pr
2.39
:
2.31
Deceleration selected indicator
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
1 to 8
Update rate
5ms
2.32
Acceleration select bit 0
2.33
Acceleration select bit 1
2.34
Acceleration select bit 2
2.35
Deceleration select bit 0
2.36
Deceleration select bit 1
2.37
Deceleration select bit 2
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Default
OFF(0)
Update rate
5ms
2.38
Unused parameter
2.39
Ramp rate units
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
Range
0 to 2
Default
1
Update rate
Background
Pr 2.39
0 to 100Hz
0 to 50Hz
0
1s
0.5s
1
10s
5s
2
100s
50s
Summary of Contents for 2202