10.14 Menu 14: PID controller
Table 10-25 Menu 14 parameters: single line descriptions
Parameter
Range
Default
Setting
Update Rate
14.01
PID output
±
100.0%
21 ms
14.02
PID main reference source
Pr
0.00
to Pr
21.51
Pr
0.00
Drive reset
14.03
PID reference source
Pr
0.00
to Pr
21.51
Pr
0.00
Drive reset
14.04
PID feedback source
Pr
0.00
to Pr
21.51
Pr
0.00
Drive reset
14.05
PID reference source invert
OFF(0) or On(1)
OFF(0)
21 ms
14.06
PID feedback source invert
OFF(0) or On(1)
OFF(0)
21 ms
14.07
PID reference slew rate limit
0.0 to 3200.0 s
0.0
B
14.08
PID enable
OFF(0) or On(1)
OFF(0)
21 ms
14.09
Optional PID enable source
Pr
0.00
to Pr
21.51
Pr
0.00
Drive reset
14.10
PID proportional gain
0.000 to 4.000
1.000
21 ms
14.11
PID integral gain
0.000 to 4.000
0.500
21 ms
14.12
PID derivative gain
0.000 to 4.000
0.000
21 ms
14.13
PID high limit
0.0 to 100.0%
100.0
21 ms
14.14
PID low limit
±
100.0%
-100.0
21 ms
14.15
PID scaling
0.000 to 4.000
1.000
21 ms
14.16
PID output destination
Pr
0.00
to Pr
21.51
Pr
0.00
Drive reset
14.17
PID hold integrator
OFF(0) or On(1)
OFF(0)
21 ms
14.18
Select symmetrical limit on PID
OFF(0) or On(1)
OFF(0)
21 ms
14.19
PID Main reference
±
100.0%
21 ms
14.20
PID reference
±
100.0%
21 ms
14.21
PID feedback
±
100.0%
21 ms
14.22
PID error
±
100.0%
21 ms