90
Scout 320 REV 3:2018
8.2 HMI Alarm Message
Alarm Number
CURE
※
Remove obstruction.
※
Channel section not in place properly.
※
Check the value of long feed safety is correct.
※
Check the turret stop location is correct. Set too far.
※
Check the value of short feed safety is correct.
※
Check the turret stop location is correct, set to short.
※
Possible obstruction of the pusher or bar from obtaining
position.
※
During bar change the lathe chuck signal is received prior to bar
change is finished.
※
Check bar feed cycle start signal for correct setting. This should
come on when bar change is complete.
※
Lathe does not recognize bar feeder is in bar change. Check
the End of Bar signal to the lathe is set correctly
※
Check lathe programming for incorrect process. Lathe does not
recognize bar change is in process.
※
Check material removal from lathe collet is not impeded.
※
Check bar feeder collet tension.
※
Check MAVD/AVD open position to allow for remnant removal.
※
Check telescoping nose and transition zones for possible
obstructions
※
Alarm can be produced when an alarm on the bar feeder is
produced which causes the lathe to set an alarm. Check for bar
feeder alarm as well.
※
Lathe is in alarm, reset condition for lathe alarm.
※
Check remnant is stuck or jammed in grippers or collet.
※
Remnant not removed from grippers, collet tension too high.
※
Remnant too long to fall into tray.