KGL Operating Manual – VS 3010 BS
2018-07-02
/
15 178
2 System design VS 3010 BS
The base module of the pack controller consists of an analogue module and a digital input/output module.
The controller is a modular design and can be extended with a maximum of 3 SIOX extension modules, see
picture. The following expansion stages are possible:
The device configuration and terminal assignment of the pack controller can be found in the chapter
.
BS connection and terminal assignment, page 105
VS 3010 BS Base Module
Digital inputs
23 x input 230 V AC
Relay outputs
6 x normally open contact 230 V AC
4 x changeover contact 230 V AC
Manual control switch
For manual override
Analogue Inputs / Outputs
2 x input Pt1000 - 4-wire Pt1000 temperature sensor connection (room and outdoor temperature)
13 x input Pt1000 - 2-wire Pt1000 temperature sensor connection (e.g. cylinder head temperature)
7 x input / 4..20 mA (0..10 V) - e.g. pressure transducer connection
4 x output / 0..10 V (4..20 mA) - e.g. connection for continuous compressor / condenser control
SIOX Supply - power supply for SIOX extension module
Interfaces