KGL Operating Manual – VS 3010 BS
2018-07-02
/
138 178
CONFIG ID:
XXXXX
Input
Default
Dim.
Text oil/HP fault
Z1 →
Selection of the message text that will be output in the case of oil pressure or high-pressure
compressor fault
→
Screen 3-
1-f
-
Anz.Verd. Z2 X
Input of the number of Z2 compressors
1..4/8
4/8
-
AnzVerd.m.LS
Z2
Input of the number of compressors with capacity stages Z2
1..3
1
-
Anz L-Stufen Z2
X
Input of the number of capacity stages / compressors in Z2
1..3
1
-
Bypass inv. Z2
X
Inversion of the function of the valves for capacity control (bypass) in Z2
Y/N
N
-
Freig. Z2-Verd.
→
Display enabling compressor stages Z2
→
Screen 3-
1-g
-
Ver.m.LA.AUS.
Z2 X
For load shedding and capacity-controlled compressors in Z2: shut down compressor completely or
only shut down compressor capacity stage
Y/N
N
-
Mot.sch.Verd.Z2
X
Enable motor overload cutout Z1 YES/NO Only visible if Mot.cutout C Y
Y/N
N
-
Motsch.sperr.Z2
Enable motor overload cutout Z2 YES/NO
Y/N
Y
-
Oil/HP fault Z2
X
Oil pressure difference switch / HP switch compressor YES/NO
Y/N
N
-
Text oil/HP fault
Z2 →
Selection of the message text that will be output in the case of oil pressure or high-pressure
compressor fault
→
Screen 3-
1-h
-
No. cond.stages
X
Number of condenser stages
1..4/8
4/8
-
Enable cond.
stages →
Display of the condenser stages
→
Screen 3-
1-i
Ht. rec. mode
Ht. rec. mode YES/NO, see chapter
Y/N
N
-
Room temp.
XXX
Enable room temperature sensor ON/OFF
ON
/OFF
ON
-
Outdoor temp.
XXX
Enable outdoor temperature sensor ON/OFF
ON
/OFF
ON
-
Humidity XXX
Enable humidity sensor ON/OFF
ON
/OFF
OFF
-
Kn.Nr Umgeb.
dat XX
CAN bus address (node number) of the pack controller of which the ambient data should be used.
1..9,
–
---
-
HP Transducer
Z2 XXX
Enable of the HP-Z2 pressure transducer ON/OFF
ON
/OFF
-
signal setvalue
X
Toggle setpoint signal
0 = Low active
1 = High active
0/1
1
-
Screen 3-1-a Transducer / sensor match
TRANSDUCER ID:
XXXXX
Input
Default
Dim.
LP Z1 Transducer →
Selection of operating mode of the LP Z1 pressure transducer (4..20 mA or 0..10
V)
→
Screen 3-1-a-a
LP Z1 Min XXX b
Pressure for 4 mA / 0 V at the output of the pressure transducer
0..2.0
1.0
bar
LP Z1 Max XXX b
Pressure for 20 mA / 10 V at the output of the pressure transducer
8..80.0
10.0
bar
LP Z2 Transducer →
Selection of operating mode of the LP Z2 pressure transducer (4..20 mA or 0..10
V)
→
Screen 3-1-a-b
LP Z2 Min XXX b
Pressure for 4 mA / 0 V at the output of the pressure transducer
0..2.0
1.0
bar
LP Z2 Max XXX b
Pressure for 20 mA / 10 V at the output of the pressure transducer
8..80.0
10.0
bar