6.2.4 Terminal assignment of the analogue inputs
Connection: Only on the base module – terminal blocks bottom left – 22 analogue inputs
Warning about dangerous electrical voltage! Danger of electric shock! If voltage is applied to the
analogue inputs,there is a danger of personal injury as the analogue inputs are not galvanically
isolated from other system components (e.g. pressure transmitter). Furthermore, this will destroy the
controller!
Malfunctions due to interference! All supply lines from and to the pack controller (with the exception
of the 230 V power supply and signal lines) must be shielded (cable type LiYCY)! This particularly
applies for the analogue inputs and outputs (e.g. sensor supply cables) as well as for the CAN bus
cabling (see
).As a general rule, care should
Basics and General Safety and Connection Instructions
be taken to ensure that signal cables and cables carrying mains voltage are routed in separate cable
channels.
Terminal No.
Function
Base module
2 x Pt1000 4-wire temperature sensor
1
2
3
4
Outdoor temperature
V+
+
-
V-
5
6
7
8
Room temperature
V+
+
-
V-
13 x Pt1000 2-wire temperature sensor
9, 10
11, 12
13, 14
15, 16
17, 18
19, 20
21, 22
23, 24
Cylinder head temperature C1
Cylinder head temperature C2
Cylinder head temperature C3
Cylinder head temperature C4
Cylinder head temperature C5
Cylinder head temperature C6
Cylinder head temperature C7
Cylinder head temperature C8
25, 26
Temperature sensor R4.1