KGL Operating Manual – VS 3010 BS
2018-07-02
/
88 178
5.2.2 Default settings with S1
Coding switch 1 setting
DIP switch S1 coding switch 1 specifies the Pack Type NT (normal temperature) and LT (low temperature):
DIP switch S1
Coding switch 1
Switch position
Pack type
ON
not used
OFF
not used
Coding switches 2 and 3 setting - number of extension modules with manual control switch (number of
capacity stages)
DIP switch S1 coding switches 2 and 3 specify the maximum number of compressor and fan capacity stages.
4 compressors and 4 fans can be controlled in the base module.
An additional SIOX extension module is required for up to 8 compressor and 8 fan capacity stages; another
second SIOX extension module is required for up to 12 compressor and 12 fan capacity stages.
DIP switch S1
Coding switch 2
Switch position
Coding switch 2
ON
1 external SIOX extension module
max. 8 compressor stages
max. 8 fans
OFF
no SIOX extension module
max. 4 compressor stages
max. 4 fans
DIP switch S1
Coding switch 3
Switch position
Pack type
ON
not used
OFF
not used
A maximum of 12 compressors and 12 fans can be used, see chapter
.