KGL Operating Manual – VS 3010 BS
2018-07-02
/
140 178
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-1-f Selection of text for oil/HP fault in Z1
T.Oil/HP-F ID: XXXXX
Input
Default
Dim.
Oil diff. pr. Cx √
The selected message text is output in the event of any fault detected via the
compressor x oil / HP
fault digital inputs
√
√
-
HP-Fault Cx
-
-
Oil/HP-Fault Cx
-
-
Screen 3-1-g Freig. Z2-Verd. (enable of the capacity stages Z2)
Z2-VERD. ID: XXXXX
Input
Default
Dim.
Lst.Stufe 1 XXX
Capacity stage 1
ON/OFF
ON
-
...
Only the available capacity stages (depending on configuration) are displayed.
Comp. stage n XXX
Capacity stage n
ON/OFF
-
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-1-h Selection of text for oil/HP fault in Z2
T.Oil/HP-F ID: XXXXX
Input
Default
Dim.
Oil diff. pr. Cx √
The selected message text is output in the event of any fault detected via the
compressor x oil / HP
fault digital inputs
√
√
-
HP-Fault Cx
-
-
Oil/HP-Fault Cx
-
-
Screen 3-1-e Enable of the condenser stages
ENABL.COND ID: XXXXX
Input
Default
Dim.
Verf.Stufe 1 XXX
Condenser stage 1
ON/OFF
ON
-
...
Only the available condenser stages (depending on configuration) are displayed.
Verfl.Stufe n XXX
Condenser stage n
ON/OFF
ON
-
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Menu 3-2 Regulation
SETPOINTS ID: XXXXX
1 LP control
Continue to menu 3-2-1
2 HP control
Continue to menu 3-2-2
3 Cascade regulation *
Continue to menu 3-2-3
* The function must be activated in menu 3-1.
Menu 3-2-1 LP control
LP-Control ID: XXXXX
1 Compressor control Z1
Continue to menu 3-2-1-1