KGL Operating Manual – VS 3010 BS
2018-07-02
/
86 178
2. CAN bus address selector switch S2
Setting of the CAN bus address or node number (Node No.) position 1..9 address 101..109
Deactivation as CAN bus node position 0 no addressing
For details, see chapter
Setting the CAN bus address with S2, page 90
3. Jumper J1 for the activation of the interfaces
Configured to RS485 at the factory
RS485 (terminals 13..16) factory setting , for control of EBM fans, in the future for connection to the
BCS (building control system)
TTY (terminals 9..12) for the communication in the LDS1 system.
Any change of the jumper J1 is usually not necessary. For further information, see
the interface RS485/TTY using jumper J1, page 90
5.2.1 SIOX extension module - for DIN rail mounting
A maximum of 3 SIOX ( erial
E tension) extension modules can be connected to the pack controller. The
S
IO x
pack controller as well as the SIOX extension modules have manual control switches so that the regulation
can be manually overridden in emergency operation, see chapter
Manual / automatic emergency mode
. Each SIOX extension module extends the pack controller by an additional 12 digital
inputs and 8 relay outputs. The number of connected SIOX modules must be configured, see chapter
Only SIOX extension modules with manual control switch may be connected.
SIOX extension modules
!
without manual control switch are not authorised
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be ensured that
is present at all connections of the controller.
no voltage
Wiring of the digital inputs: All digital inputs of the SIOX extension module must be set to 230 V AC
for the operation.
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of
the control component.