KGL Operating Manual – VS 3010 BS
2018-07-02
/
84 178
5 VS 3010 BS Installation and start-up
Important safety information! Before the installation and start-up of the controller, the chapter
must be carefully read in its entirety and all safety instructions and hazard
warnings observed. Any maintenance by the user is not intended as possible hazards from incorrect
re-assembly cannot be ruled out. Opening the device is not authorised! Furthermore, it must be noted
that the safety of the system or the installation in which the device is integrated is the responsibility of
the creator of the system or installation. If the device is used in any way not specified by Eckelmann
AG, the protection supported by the device can be compromised!
The system centre, the operator terminal and the PC software LDSWin are used for the configuration of the
controller for the start-up and for later changes.
The controller should only be used with compatible versions of the PC software LDSWin, otherwise
the scope of functions can be restricted.
: The
should always be used.
Tip
Furthermore, actual values and archived long-term data can be displayed. Default hardware and software
settings must be made on the pack controller before the start-up of the system.
5.1 DIN rail mounting
The pack controller is available as version for DIN rail mounting. It is snapped on / fastened to the DIN rail
using two claws (on the underside of the device). The power loss of the device is 24 VA. This must be taken
into account for the installation. The pack controller can be put into operation after completion of the
mechanical and electrical installation.
The pack controller may only be mounted on a DIN rail and operated as an integrated regulation and
control device (EN60730). All supply lines from and to the device (with the exception of the 230 V
power supply and signal lines) must be shielded! This particularly applies for the analogue inputs
(sensor supply lines) as well as for the CAN bus cabling (cable type: LiYCY (TP)). These must also
be installed with sufficiently large distance from live cables. This prevents faulty measurements and
protects the device against electrical interference via the analogue inputs.
Protection type and dimensions can be found in the chapter
Technical Data VS 3010 BS / SIOX,
.
5.2 Default hardware settings
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be ensured that
is present at all connections of the controller.
no voltage
Wiring of the digital inputs: All digital inputs of the pack controller must be set to 230 V AC for the
operation.
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of