KGL Operating Manual – VS 3010 BS
2018-07-02
/
135 178
Z2-VERD. ID: XXXXX
Handsch. Smax XXX
ON-OFF-AUTOMATIC max compressor stage manual control switch
Comp. stage max
XXX
Max compressor stage digital output
Base module: max. number of total compressor stages: 4
with first SIOX extension module max. number of total compressor stages: 8
Z1 compressors: 1..n compressor stages: 1..max. 3/7, depending on system configuration
Z2 compressors: n+1..max. compressor stages: 2..max. 4/8, depending on system configuration
Number of Z1 compressor number of Z2 compressor stages = max. 4/8 total compressor stages
Menu 2-4 Fans
COND FAN ID: XXXXX
M.cutout F1 XXX
Fan 1 motor overload cutout digital input
Fan F1 XXX
Fan 1 digital output
Fast speed F1 XXX
Delta operation / fast speed fan 1
...
Only the actual number of fans is displayed
Fast speed F7 XXX
Delta operation / fast speed fan 7
M.cutout F8 XXX
Fan 8 motor overload cutout digital input
Fan F8 XXX
Fan 8 digital output
Base module: Fans 1 - max. 4
(for star-delta switching: max 2 for SSFF and max 3 for SSSF)
with first SIOX extension module Fans 1 - max. 8
(for star-delta switching: max 4 for SSFF and max 7 for SSSF)
Menu 2-5 System actual values
SYSTEM ID: XXXXX
HP cutout XXX
HP cutout digital input
LP cutout Z1 XXX
LP cutout Z1 digital input
LP cutout Z2 XXX
LP cutout Z2 digital input
Burst disk XXX
Burst disk digital input
Low liq. level XXX %
Refrigerant low liquid level digital input
Ext. alarm XXX
External alarm digital input
Setp. toggle XXX
Toggle setpoint digital input
Comp/cond. unload XXX
Comp/cond. unload digital input
Load shed Z11 XXX
Load shed 1 Z1 digital input
Load shed Z12 XXX
Load shed 2 Z1 digital input
Load shed Z2 XXX
Load shed Z2 digital input
Enable Z1 XXX
Enable Z1 consumers digital output
Enable Z2 XXX
Enable Z2 consumers digital output
toggle Comp.Z1
Base load rotation of frequency controlled compressors.
Only visible when Z1 base load rotation is activated.
toggle Comp.Z2
Base load rotation of frequency controlled compressors.
Only visible when Z2 base load rotation is activated.
Freig.E-Vent.1
Enable of the EE valve 1 of the cascade controller.
Only visible when cascade controller is activated.
Freig.E-Vent.2