KGL Operating Manual – VS 3010 BS
2018-07-02
/
105 178
6 VS 3010 BS connection and terminal assignment
The illustrations and tables show the terminal assignments for the pack controller and its SIOX extension
modules. A detailed description of the connection and terminal assignment of the controller and its
components is shown below.
The following points must be strictly taken into account for the cabling:
The system must be disconnected from the power supply before detaching or inserting plug
connectors on the base module and the SIOX extension modules.
All connection cables from and to the controller – with the exception of the digital inputs and
the relay outputs – must be shielded. Otherwise malfunctions, e.g. faulty measurements,
cannot be ruled out.
Pay strict attention to the correct polarity for inputs and outputs with current or voltage
interface ((0..10 V or 4..20 mA). Short circuits or a faulty power supply can result in
impairments of the function or even destruction of components of the controller. It must also
be strictly ensured that the inputs / outputs are correctly configured using the jumpers provided
for this (current or voltage interface, see chapter
Configuration of the analogue inputs and
6.1 Pin assignments
6.1.1 Pin assignments VS 3010 BS base module