5.5.1 Necessary and optional sensors
Depending on the controller type and the operating mode, there are necessary and optional sensors for the
case controller. A sensor scan is performed automatically during the
of the controller. The number of
scanned sensors can be checked in the menu (6-1) or with the LDSWin PC software. This allows unconnected
sensors to be removed from the monitoring for sensor fault.
The following lists show required and optional sensors in the complete design:
Controller type
Sensors necessary for regulation
Optional sensors - extended functionality
(if terminal available;
see chapter
Single-zone operation
UA 121 E
UA 131 E / UA 131 E LS
UA 141E
Zone 1: R1.1, R2.1, R4.1, R6.1
Zone 1: R5.1
R1.2, R2.2, R4.2, R5.2, R6.2 (or R4.3, R4.4)
UR 141 NE
UR 141 TE
Zone 1: R1.1, R4.1, R6.1
Zone 1: R2.1, R5.1
R1.2, R2.2, R4.2, R5.2, R6.2
UK 100 E **
KR 160 E **
Zone 1: R4.1, R6.1
Zone 1: R1.1, R5.1
R1.2, R4.2, R5.2, R6.2
Two-zone operation - only UA 400 E CC / UA 410 E AC
UA 121 E
UA 131 E / UA 131 E LS
UA 141E
Zone 1: R1.1, R2.1, R4.1, R6.1
Zone 2: R1.2, R2.2, R4.2, R6.2
Zone 1: R5.1 (or R4.3)*
Zone 2: R5.2 (or R4.4)*
UR 141 NEUR 141 TE
Zone 1: R1.1, R4.1, R6.1
Zone 2: R1.2, R4.2, R6.2
Zone 1: R2.1, R5.1
Zone 2: R2.2, R5.2
UK 100 E **
KR 160 E **
Zone 1: R4.1, R6.1
Zone 2: R4.2, R6.2
Zone 1: R1.1, R5.1
Zone 2: R1.2, R5.2
*only UA 131 E LS for
operation with 4 return air sensors
(R4.3 / R4.4 are activated)
** only UA 410 E AC
•
•
ATTENTION
Compressor damage! Danger due to liquid refrigerant on the suction side of the compressor!
Operating mode
t
0
via CAN bus
(menu 6-2-6)
The evaporator inlet sensors R5.1 and R5.2 should also be connected in the
t
0
via CAN
bus
operating mode. This results in improved emergency running characteristics in the event of
failure of the CAN bus transmission. In standalone operation (without local pressure transmitter),
the sensors, R5.1 and R5.2
must
be connected; see chapter
Operating mode
t
0
local Z1 / Z2
(menu 6-2-6)
In the case of evaporators with high cooling capacity which require
high control dynamics
, the
superheat control should be realised via a local pressure transmitter (only UA 410 E AC); see
chapters
Standalone operation using activated local pressure transmitter
and
Superheat control only via sensors R5.1 and R5.2 is not recommended, as there is a risk of
evaporator flooding due to the slow response behaviour!
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...